For: operators of stores and facilities, equipment maintenance contractors and IT teams that use the Danfoss AK-SM 800A series of refrigeration and HVAC system managers. This article is based on CISA's KEV data, the CVE records and the page from the coordinating CSIRT that assigned the CVEs. It does not cover attack steps.
続報待ち:この記事は公式発表に合わせて更新します
- Who is affected
operators of stores and facilities, equipment maintenance contractors and IT teams that use the Danfoss AK-SM 800A series of refrigeration and HVAC system managers.
- Confirmed so farSee the table ↓
- The flaws
- KEV listing
- Not yet confirmed
- The scale, method and actors of the exploitation (KEV only indicates that exploitation was confirmed)
- Whether the flaws have been used in ransomware attacks (KEV lists this as unknown)
- The text of Danfoss's advisories (this site could not access DSA-2023-08-01 or DSA-2025-03-01, so version information comes from the CVE records and the CSIRT page)
- What to do nowSee the steps ↓
- List the affected devices
- Check the version and update
- Make it unreachable directly from the internet
1 more
- If it was exposed, investigate as if compromised
- Where to verify (source)All sources ↓
- CISA
- Last checked
- As of November 26, 2026
Follow-up plans and what we checked
CISA added the three AK-SM 800A series flaws to KEV on November 25, 2026. The deadlines are November 28 for CVE-2023-25915 and CVE-2023-25914 (three days after being added) and December 9 for CVE-2025-41450. The first two are flagged for forensic triage. KEV asks for mitigations as instructed by the vendor, or to stop using the product if none are available, and tells agencies to evaluate each asset's internet exposure. The Dutch CSIRT that assigned the 2023 CVEs disclosed them in August 2023. It says it began scanning the internet for vulnerable devices at the time of disclosure and, from September 2023, began notifying owners of vulnerable devices.
What to do today
The steps from the CVE records and the CSIRT page come first; this site's additions follow.
List the affected devices
List the AK-SM 800A series devices at each store and facility (in the CVE records, the two 2023 flaws name the AK-SM800A and the 2025 flaw names the AK-SM 8xxA series). Devices are often installed and managed by equipment maintenance contractors, so ask them for a list, the device versions, and whether each device is connected to the internet (this site's addition). The asset inventory checklist can help.
Check the version and update
According to the CVE records, CVE-2023-25915 and CVE-2023-25914 affect versions before 3.3. The CSIRT page says Danfoss recommends installing the latest patch, 3.3. CVE-2025-41450 affects versions before 4.2. Since 4.2 is later than 3.3, this site reads it that updating to 4.2 or later covers all three (we could not confirm the text of Danfoss's advisories; check the update procedure and target versions with Danfoss or your maintenance contractor).
Make it unreachable directly from the internet
This is this site's addition. Block connections to the device's admin interface and XML interface from the internet, and limit them to a maintenance VPN or the addresses of specific sites. Check that no port forwarding to the device is left on the router. Do this first, even if the update will take time.
If it was exposed, investigate as if compromised
The CVE record for CVE-2023-25914 says the information that can be read can lead to full system compromise. For devices that were reachable from outside, look for accounts or setting changes you do not recognize and review the activity records, then replace the device's passwords and any other credentials stored on it. Also check whether the same passwords are reused on other devices or systems (this site's addition). If you find suspicious signs, follow the vulnerability response playbook and contact your maintenance contractor or outside specialists.
What the vulnerabilities are
- Product
- Danfoss AK-SM 800A series (refrigeration and HVAC system managers)
- CVE-2023-25915
- An authenticated user can run arbitrary commands (improper input validation, CWE-20). CVSS v3.1 9.9 (AV:N/AC:L/PR:L/UI:N/S:C). Versions before 3.3. KEV deadline November 28
- CVE-2023-25914
- An authenticated user can read system files of the device through the XML interface (path traversal, CWE-22). CVSS v3.1 8.8. Versions before 3.3. KEV deadline November 28
- CVE-2025-41450
- Improper authentication (CWE-305). Per KEV's description, a web report containing sensitive information, including internal IP addresses, usernames and store names, can be generated. CVSS v3.1 8.2 (AC:H/PR:N/UI:R). Versions before 4.2. KEV deadline December 9
- Fix
- 3.3 for the two 2023 flaws; 4.2 for the 2025 flaw (CVE records)
- Exploitation
- All three are in KEV. Ransomware use: unknown
- How it works, in short: the two 2023 flaws let someone who can log in to the device (low privileges are enough) run commands on the device's operating system or read its system files. The 2025 flaw is an authentication failure that allows a web report with sensitive information to be generated. We do not publish the specific methods.
- What confirmed exploitation means: KEV indicates that exploitation was confirmed. The scale, method and actors have not been disclosed.
- This site's view: this is the pattern of an old flaw exploited more than three years after publication. Unlike PCs and servers, refrigeration and HVAC managers are rarely updated once installed and tend to stay under the control of the contractor that installed them. Devices that stopped receiving updates and remain on the internet become the entry point. The defenses come down to two things: updating, and reducing exposure to the internet. Similar cases on edge devices are collected in Exploited edge device vulnerabilities, mid-October 2026.
- Priority: first find out whether any device is reachable from the internet. If one is, cut that off before updating. Devices that are not reachable can have their versions checked and be updated during regular maintenance.
What is known and what is not
| Item | Details | Status |
|---|---|---|
| The flaws | Authenticated command execution, authenticated system file reading, a web report generated through an authentication failure | Confirmed (CVE records, KEV) |
| KEV listing | All three on November 25, 2026. Deadlines November 28 (two) and December 9 (one) | Confirmed (KEV) |
| Fixed versions | 3.3 for the two 2023 flaws, 4.2 for the 2025 flaw | CVE records. Danfoss advisory text not confirmed |
| Whether 4.2 or later fixes all three | 4.2 is later than 3.3 | This site's reading (unconfirmed) |
| Scale and method of exploitation | Not disclosed | Unknown |
| Use in ransomware | KEV lists it as unknown | Unknown |
| CVE-2023-25913, found in the same research | Listed on the CSIRT page. Not in this KEV addition | Details not confirmed |
Sources
- CISA — Known Exploited Vulnerabilities Catalog (three entries added November 25, 2026; deadlines, forensic triage flags, ransomware use "unknown")
- Danfoss — DSA-2023-08-01 and DSA-2025-03-01 (the vendor advisories referenced by KEV; this site's access was denied and the text could not be confirmed)
- The Dutch CSIRT that assigned the CVEs — DIVD-2023-00025 (the 2023 timeline, the recommended version 3.3, scanning for and notification of vulnerable devices)
- CVE.org — CVE-2023-25915, CVE-2023-25914 and CVE-2025-41450 (affected versions, CVSS, descriptions)
Attack steps and indicators of compromise (IOCs) are not included. Last checked: November 26, 2026.
Update history
2026-11-26: First version, based on CISA's KEV data, the CVE records and the page from the CSIRT that assigned the CVEs. The text of Danfoss's advisories could not be accessed and is unconfirmed.